Features a high accuracy over a wide range with a superior phase shift that is ideal for areas where space is limited such as when metering multiples loads within an electrical panel. Offers a 20A amp rating.
Features a high accuracy over a wide range with a superior phase shift that is ideal for areas where space is limited such as when metering multiples loads within an electrical panel. Offers a 20A amp rating.
Features
Applications
Key Specifications | |
Window Size | 0.4" (10 mm) |
Current Range | 0.25 to 40A AC |
Output | 333 mV @ 20A AC 16.65 mV/A AC |
Ratio Error | <0.5% from 0.25 to 40A AC (typical) |
Phase Error | <1.5° from 1 to 40A AC <2° from 0.25 to 1A AC |
Electrical | |
Output | 333 mV @ 20 A |
Wire Polarity | White = Hi, positive (+) Black = Low, negative (-) |
Phasing Orientation | Arrow on case points toward load |
Frequency Range | 50 to 400 Hz |
Mechanical | |
Case Material | White Nylon, UL 94 V‐0 |
Leads | 2.4 m (8'), 600V, 20 gauge |
Working Temperature | 5 to 140°F (‐15 to 60°C) |
Key Specifications | |
Window Size | 0.4" (10 mm) |
Current Range | 0.25 to 40A AC |
Output | 333 mV @ 20A AC 16.65 mV/A AC |
Ratio Error | <0.5% from 0.25 to 40A AC (typical) |
Phase Error | <1.5° from 1 to 40A AC <2° from 0.25 to 1A AC |
Electrical | |
Output | 333 mV @ 20 A |
Wire Polarity | White = Hi, positive (+) Black = Low, negative (-) |
Phasing Orientation | Arrow on case points toward load |
Frequency Range | 50 to 400 Hz |
Mechanical | |
Case Material | White Nylon, UL 94 V‐0 |
Leads | 2.4 m (8'), 600V, 20 gauge |
Working Temperature | 5 to 140°F (‐15 to 60°C) |