Energy meter connects easily to control/data systems networs using Modbus protocol. Status LEDs provide quick confirmation of successful installation.
Energy meter connects easily to control/data systems networs using Modbus protocol. Status LEDs provide quick confirmation of successful installation.
Features
Applications
Connection | |
RS-485 | Up to 63 devices |
2-wire or 4-wire | Field selectable |
Baud Rate | 2400, 4800, 9600, 19200 baud, selectable |
Parity | None/odd/even, selectable |
Address Range | DIP switch selectable (1 to 63) |
External Inputs | |
Demand Syncronizing or Pulse Counting | Field selectable |
Wiring | |
Terminal Block Screw Torque | 0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) maximum |
Terminal Block Wire Dimensions | 26 to 14 AWG (0.13 to 2.08 mm²) |
Environmental Conditions | |
Temperature | Operating: 32 to 122°F (0 to 50°C) Storage: -40 to 158°F (-40 to 70°C) |
Humidity Range | 0 to 95% RH (non-condensing) |
Altitude of Operation | 0 to 2000 m |
Connection | |
RS-485 | Up to 63 devices |
2-wire or 4-wire | Field selectable |
Baud Rate | 2400, 4800, 9600, 19200 baud, selectable |
Parity | None/odd/even, selectable |
Address Range | DIP switch selectable (1 to 63) |
External Inputs | |
Demand Syncronizing or Pulse Counting | Field selectable |
Wiring | |
Terminal Block Screw Torque | 0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) maximum |
Terminal Block Wire Dimensions | 26 to 14 AWG (0.13 to 2.08 mm²) |
Environmental Conditions | |
Temperature | Operating: 32 to 122°F (0 to 50°C) Storage: -40 to 158°F (-40 to 70°C) |
Humidity Range | 0 to 95% RH (non-condensing) |
Altitude of Operation | 0 to 2000 m |