Save time with this digital multifunctional ground resistance tester that uses just two probes on the ground connector to measure the current circulation value of the earth/ground. Moreover, this tester uses an automated Fall-of-Potential method, stores measurements, and includes a USB drive for Dataview software.
Save time with this digital multifunctional ground resistance tester that uses just two probes on the ground connector to measure the current circulation value of the earth/ground. Moreover, this tester uses an automated Fall-of-Potential method, stores measurements, and includes a USB drive for Dataview software.
The AEMC 6472 Multi-Function Digital Ground Resistance Tester is a portable measurement instrument designed to measure Bond Resistance, Ground Resistance (with and without clamps), Soil Resistivity, Earth Coupling, Step & Touch Potential.
The AEMC 6472 measures from 0.01 to 99.99 kΩ and is auto-ranging, automatically seeking out the optimum measurement range, test frequency and test current. The adjustable test frequency (either manual or automatic) from 40 to 5078Hz test voltage provides rejection of high levels of interference, allowing it to be used under difficult conditions such as the presence of high stray currents that normally affect accuracy.Up to 512 test results can be stored in internal memory for later recall to the display or downloaded to a PC using DataView® software (included) for Automatic Report Generation, Automatic Fall-of-Potential Plot Generation, Frequency/Resistance Plots and much more.
Features
Applications
3-Pole Measurement | |
Range (Auto-Ranging) | 0.09 Ω to 99.9 kΩ |
Resolution | 0.01 to 100 Ω |
Test Voltage | Nominal 16 or 32 VRMS user selectable |
Resistance Measurement Frequency | 41 to 5078 Hz automatic or user selectable |
Test Current | Up to 250 mA |
Accuracy | ±2% of Reading + 1 ct @ 128 Hz |
2 Clamp Measurement | |
Range | 0.01 to 500 Ω |
Resolution | 0.01 to 1 Ω |
Measurement Frequency | Auto: 1611 Hz Manual: 128, 1367, 1611, 1758 Hz |
Soil Resistivity 4-Pole Measurement | |
Test Method | Wenner or Schlumberger selectable with automatic calculation of test results in Ω-meters |
Range (Auto-Ranging) | 0.01 to 99.99 kΩ ρ Max: 999 kΩm |
Resolution | 0.01 to 100 Ω |
Test Voltage | 16 or 32 V user selectable |
Frequency | From 41 to 128 Hz selectable |
Click on a category to view a selection of compatible accessories with the AEMC 6472 Ground Resistance Tester Multifunction with 2, 3, and 4-point, bond test and DataView software, 0.09 Ω to 99.9 kΩ, 41 to 5078 Hz.
3-Pole Measurement | |
Range (Auto-Ranging) | 0.09 Ω to 99.9 kΩ |
Resolution | 0.01 to 100 Ω |
Test Voltage | Nominal 16 or 32 VRMS user selectable |
Resistance Measurement Frequency | 41 to 5078 Hz automatic or user selectable |
Test Current | Up to 250 mA |
Accuracy | ±2% of Reading + 1 ct @ 128 Hz |
2 Clamp Measurement | |
Range | 0.01 to 500 Ω |
Resolution | 0.01 to 1 Ω |
Measurement Frequency | Auto: 1611 Hz Manual: 128, 1367, 1611, 1758 Hz |
Soil Resistivity 4-Pole Measurement | |
Test Method | Wenner or Schlumberger selectable with automatic calculation of test results in Ω-meters |
Range (Auto-Ranging) | 0.01 to 99.99 kΩ ρ Max: 999 kΩm |
Resolution | 0.01 to 100 Ω |
Test Voltage | 16 or 32 V user selectable |
Frequency | From 41 to 128 Hz selectable |
Click on a category to view a selection of compatible accessories with the AEMC 6472 Ground Resistance Tester Multifunction with 2, 3, and 4-point, bond test and DataView software, 0.09 Ω to 99.9 kΩ, 41 to 5078 Hz.