General-purpose, panel mount power and energy meter with integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input.
General-purpose, panel mount power and energy meter with integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
The Accuenergy Acuvim II multifunction power and energy meter is used for the metering of distribution feeders, generators, motors, transformers, and more. This model includes the Acuvim II basic unit with field selectable 5A or 1A input, 100 to 415V AC, 50/60Hz, 100 to 300V DC power supply, and an integrated mounting option with LCD display. The Acuvim II is ideal for use with medium and low voltage systems in a variety of commercial, industrial, and utility applications.
Accuracy Acuvim-II |
Accuracy Acuvim-IIR/IIE/IIW |
Resolution | Range | |
---|---|---|---|---|
Voltage | 0.2% | 0.2% | 0.1V | 20V~1000kV |
Current | 0.2% | 0.2% | 0.1mA | 5mA~50000A |
Power | 0.5% | 0.2% | 1W | -9999MW~9999MW |
Reactive Power | 0.5% | 0.2% | 1var | 9999Mvar~9999Mvar |
Apparent Power | 0.5% | 0.2% | 1VA | 0~9999MVA |
Power Demand | 0.5% | 0.2% | 1W | -9999MW~9999MW |
Reactive Power Demand | 0.5% | 0.2% | 1var | -9999Mvar~9999Mvar |
Apparent Power Demand | 0.5% | 0.2% | 0.2% | 0~9999MVA |
Power Factor | 0.5% | 0.2% | 0.001 | -1.000~1.000 |
Frequency | 0.2% | 0.2% | 0.01Hz | 45.00~65.00Hz |
Energy Primary | 0.5% | 0.2% | 0.1kWh | 0-99999999.9kWh |
Energy Secondary | 0.5% | 0.2% | 0.001kWh | 0-999999.999kWh |
Reactive Energy Primary | 0.5% | 0.2% | 0.1kvarh | 0-99999999.9kvarh |
Reactive Energy Secondary | 0.5% | 0.2% | 0.001kvarh | 0-999999.999kvarh |
Apparent Energy Primary | 0.5% | 0.2% | 0.1kVAh | 0-99999999.9kVAh |
Apparent Energy Secondary | 0.5% | 0.2% | 0.001kVAh | 0-999999.999kVAh |
Harmonics | 1.0% | 1.0% | 0.1% | 0.0%~100.0% 20.0%~100.0% (IIR/IIE/IIW) |
Phase Angle | 2.0% | 2.0% | 0.1° | 0.0°~359.9° |
Unbalance Factor | 2.0% | 2.0% | 0.1% | 0.0%~100.0% |
Running Time | 0.01h | 0~9999999.99h |
Current Inputs (Each Channel) | |
---|---|
Nominal Current | 5A /1A |
Metering Range | 0~10A AC |
Withstand | 20Arms continuous, 100Arms for 1 second, non-recurring |
Burden | 0.05VA (typical) @ 5Arms |
Pickup Current | 0.1% of nominal |
Accuracy | 0.2% full scale |
Voltage Inputs (Each Channel) | |
Nominal Full Scale | 400V AC L-N, 690V AC L-L (+20%) |
Withstand | 1500V AC continuous 2500V AC, 50/60Hz for 1 minute |
Input Impedance | 2Mohm per phase |
Metering Frequency | 45Hz~65Hz |
Pickup Voltage | 10Vac (30 Vac for Acuvim IIR/IIE/IIW) |
Accuracy | 0.2% full scale |
Energy Accuracy (Acuvim IIR/IIE/IIW) | |
Active | According to IEC 62053-22: Class 0.2s According to ANSI C12.20: Class 0.2s |
Reactive (according to IEC 62053-23) | Class 2 |
Harmonic Resolution | |
Metered Value | Acuvim II: 31st harmonic Acuvim IIR/IIE/IIW: 63rd harmonic |
Control Power | |
Universal | AC or DC |
Operating Range | 100~415V AC, 50/60Hz 100~300V DC |
Burden | 5W |
Frequency | 50/60Hz |
Withstand | 3250V AC, 50/60Hz for 1 minute Installation Category III (Distribution) |
Low Voltage DC Control Power (Optional) | |
Operating Range | 20~60V DC |
Burden | 5W |
Rs-485 (standard)
MODBUS® RTU Protocol, 2-wire connection
1200~38400 baud rate
The second Rs-485 Port (Optional)
MODBUS® RTU Protocol, 2-wire connection
4800~38400 baud rate
Ethernet (Optional)
10M/100M BaseT
MODBUS® TCP/IP Protocol
Data Browsing through HTTP
Sending e-mail automatically
PROFI-BUs (Optional)
PROFIBUS-DP/V0 Protoco
Work as PROFIBUS slave, baud rate adaptive, up to 12M
Typical input bytes: 32, typical output bytes: 32
PROFIBUS standard according to EN 50170 vol.2
Category | Item | Parameters | Acuvim II | Acuvim IIR | Acuvim IIE | |
Metering | Real Time Metering | Phase Voltage | V1, V2, V3, Vlnavg | |||
Metering | Real Time Metering | Line Voltage | V12, V23, V31, Vllavg | |||
Metering | Real Time Metering | Current | I1, I2, I3, In, Iavg | |||
Metering | Real Time Metering | Power | P1, P2, P3, Psum | |||
Metering | Real Time Metering | Reactive Power | Q1, Q2, Q3, Qsum | |||
Metering | Real Time Metering | Apparent Power | S1, S2, S3, Ssum | |||
Metering | Real Time Metering | Power Factor | PF1, PF2, PF3, PF | |||
Metering | Real Time Metering | Frequency | F | |||
Metering | Real Time Metering | Load Features | Load Features | |||
Metering | Real Time Metering | Four Quadrant Powers | Four Quadrant Powers | |||
Metering | Energy & Demand | Energy | Ep_imp, Ep_exp, Ep_total, Ep_net | |||
Metering | Energy & Demand | Reactive Energy | Eq_imp, Eq_exp, Eq_total, Eq_net | |||
Metering | Energy & Demand | Apparent Energy | Es | |||
Metering | Energy & Demand | Demand | Dmd_P, Dmd_Q, Dmd_S, Dmd_I1, Dmd_I2, Dmd_I3 | |||
TOU | Time of Use | Energy/max demand | TOU, 4 Tariffs, 12 Seasons, 14 Schedules | |||
TOU | Daylight Savings Time | Two formats adjust | Month/Day/Hour/Minute Month/Week/First few weeks/Hour/Minute |
|||
Monitoring | Waveform Capture | voltage and current Waveform | Trigger, Manual, DI change, Sag/Dips, Swell, Over Current | |||
Monitoring | Power Quality | Voltage Unbalance Factor | U_unbl | |||
Monitoring | Power Quality | Current Unbalance Factor | I_unbl | |||
Monitoring | Power Quality | Voltage THD | THD_V1,THD_V2,THD_V3, THD_Vavg | |||
Monitoring | Power Quality | Current THD | THD_I1, THD_I2, THD_I, THD_Iavg | |||
Monitoring | Power Quality | Individual Harmonics | Harmonics 2nd to 63rd (31st for Acuvim II) | |||
Monitoring | Power Quality | Voltage Crest Factor | Crest Factor | |||
Monitoring | Power Quality | TIF | THFF | |||
Monitoring | Power Quality | Current K factor | K Factor | |||
Monitoring | Statistics | MAX with Time Stamp MIN with Time Stamp |
Each phase of V & l; Total of P, Q, S, PF & F; Demad of P,Q & S; Each phase THD of V & I; Unbalnce factor of V & I |
|||
Others | Alarm | Over/Under Limit Alarm | V, I, P, Q, S, PF, V_THD & I_THD each phase and total or average; Unbalance factor of V & I; load type; Analog Input of each channel | |||
Others | Power Quality Event logging | SAG/DIPS,SWELL | Voltage | |||
Others | Data Logging | Data Logging 1 Data Logging 2 Data Logging 3 |
F, V1/2/3/lnavg, V12/23/13/lavg, I1/2/3/n/avg, P1/2/3/sum,Q1/2/3/sum, S1/2/3/sum, PF1/2/3, PF, U_unbl, I_unbl, LoadType, Ep_imp, Ep_exp, Ep_total, Ep_net, Eq_imp, Eq_exp, Eq_total, Eq_net, Es, THD_V1/2/3/avg, THD_I1/2/3/avg, Harmonics2nd to 63rd, Crest Factor, THFF, K Factor, sequence and phaseangles, DI counter, AI, AO, Dmd P/Q/S, Dmd I1/2/3 | |||
Others | Onboard memory size | Memory | Bytes | - | 4MB | 4MB |
Others | Communication | RS485 Port, Half Duplex,Optical Isolated | Modbus®-RTU Protocol | |||
Others | Time | Real Time Clock | Year, Month, Date, Hour, Minute, Second | |||
Option Module | I/O Option | Switch Status (DI) | Digital Input (Wet) | Option | Option | Option |
Option Module | I/O Option | Power Supply for DI | 24 Vdc | Option | Option | Option |
Option Module | I/O Option | Relay Output (RO) | NO, Form A | Option | Option | Option |
Option Module | I/O Option | Digital Output (DO) | Photo-MOS | Option | Option | Option |
Option Module | I/O Option | Pulse Output (PO) | By using DO | Option | Option | Option |
Option Module | I/O Option | Analog Input (AI) | 0(4)~20mA, 0(1)~5V | Option | Option | Option |
Option Module | I/O Option | Analog Output (AO) | 0(4)~20mA, 0(1)~5V | Option | Option | Option |
Option Module | Communication | Ethernet | 10M/100M, Modbus-TCP, HTTP Webpage, Email | Option | Option | Option |
Option Module | Communication | Profibus-DP | Profibus-DP/V0 | Option | Option | Option |
Option Module | Communication | RS485 Module | Additional Modbus RTU | Option | Option | Option |
As the need to better understand power and energy consumption increases, Accuenergy continues to offer a simple and effective software compliment to our metering products. Combining their meters with the Acuview software suite allows Accuenergy to offer one of the most powerful yet cost effective metering and monitoring solutions in the market.
Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim II-D-5A-P1 Intelligent Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc.
Accuracy Acuvim-II |
Accuracy Acuvim-IIR/IIE/IIW |
Resolution | Range | |
---|---|---|---|---|
Voltage | 0.2% | 0.2% | 0.1V | 20V~1000kV |
Current | 0.2% | 0.2% | 0.1mA | 5mA~50000A |
Power | 0.5% | 0.2% | 1W | -9999MW~9999MW |
Reactive Power | 0.5% | 0.2% | 1var | 9999Mvar~9999Mvar |
Apparent Power | 0.5% | 0.2% | 1VA | 0~9999MVA |
Power Demand | 0.5% | 0.2% | 1W | -9999MW~9999MW |
Reactive Power Demand | 0.5% | 0.2% | 1var | -9999Mvar~9999Mvar |
Apparent Power Demand | 0.5% | 0.2% | 0.2% | 0~9999MVA |
Power Factor | 0.5% | 0.2% | 0.001 | -1.000~1.000 |
Frequency | 0.2% | 0.2% | 0.01Hz | 45.00~65.00Hz |
Energy Primary | 0.5% | 0.2% | 0.1kWh | 0-99999999.9kWh |
Energy Secondary | 0.5% | 0.2% | 0.001kWh | 0-999999.999kWh |
Reactive Energy Primary | 0.5% | 0.2% | 0.1kvarh | 0-99999999.9kvarh |
Reactive Energy Secondary | 0.5% | 0.2% | 0.001kvarh | 0-999999.999kvarh |
Apparent Energy Primary | 0.5% | 0.2% | 0.1kVAh | 0-99999999.9kVAh |
Apparent Energy Secondary | 0.5% | 0.2% | 0.001kVAh | 0-999999.999kVAh |
Harmonics | 1.0% | 1.0% | 0.1% | 0.0%~100.0% 20.0%~100.0% (IIR/IIE/IIW) |
Phase Angle | 2.0% | 2.0% | 0.1° | 0.0°~359.9° |
Unbalance Factor | 2.0% | 2.0% | 0.1% | 0.0%~100.0% |
Running Time | 0.01h | 0~9999999.99h |
Current Inputs (Each Channel) | |
---|---|
Nominal Current | 5A /1A |
Metering Range | 0~10A AC |
Withstand | 20Arms continuous, 100Arms for 1 second, non-recurring |
Burden | 0.05VA (typical) @ 5Arms |
Pickup Current | 0.1% of nominal |
Accuracy | 0.2% full scale |
Voltage Inputs (Each Channel) | |
Nominal Full Scale | 400V AC L-N, 690V AC L-L (+20%) |
Withstand | 1500V AC continuous 2500V AC, 50/60Hz for 1 minute |
Input Impedance | 2Mohm per phase |
Metering Frequency | 45Hz~65Hz |
Pickup Voltage | 10Vac (30 Vac for Acuvim IIR/IIE/IIW) |
Accuracy | 0.2% full scale |
Energy Accuracy (Acuvim IIR/IIE/IIW) | |
Active | According to IEC 62053-22: Class 0.2s According to ANSI C12.20: Class 0.2s |
Reactive (according to IEC 62053-23) | Class 2 |
Harmonic Resolution | |
Metered Value | Acuvim II: 31st harmonic Acuvim IIR/IIE/IIW: 63rd harmonic |
Control Power | |
Universal | AC or DC |
Operating Range | 100~415V AC, 50/60Hz 100~300V DC |
Burden | 5W |
Frequency | 50/60Hz |
Withstand | 3250V AC, 50/60Hz for 1 minute Installation Category III (Distribution) |
Low Voltage DC Control Power (Optional) | |
Operating Range | 20~60V DC |
Burden | 5W |
Rs-485 (standard)
MODBUS® RTU Protocol, 2-wire connection
1200~38400 baud rate
The second Rs-485 Port (Optional)
MODBUS® RTU Protocol, 2-wire connection
4800~38400 baud rate
Ethernet (Optional)
10M/100M BaseT
MODBUS® TCP/IP Protocol
Data Browsing through HTTP
Sending e-mail automatically
PROFI-BUs (Optional)
PROFIBUS-DP/V0 Protoco
Work as PROFIBUS slave, baud rate adaptive, up to 12M
Typical input bytes: 32, typical output bytes: 32
PROFIBUS standard according to EN 50170 vol.2
Category | Item | Parameters | Acuvim II | Acuvim IIR | Acuvim IIE | |
Metering | Real Time Metering | Phase Voltage | V1, V2, V3, Vlnavg | |||
Metering | Real Time Metering | Line Voltage | V12, V23, V31, Vllavg | |||
Metering | Real Time Metering | Current | I1, I2, I3, In, Iavg | |||
Metering | Real Time Metering | Power | P1, P2, P3, Psum | |||
Metering | Real Time Metering | Reactive Power | Q1, Q2, Q3, Qsum | |||
Metering | Real Time Metering | Apparent Power | S1, S2, S3, Ssum | |||
Metering | Real Time Metering | Power Factor | PF1, PF2, PF3, PF | |||
Metering | Real Time Metering | Frequency | F | |||
Metering | Real Time Metering | Load Features | Load Features | |||
Metering | Real Time Metering | Four Quadrant Powers | Four Quadrant Powers | |||
Metering | Energy & Demand | Energy | Ep_imp, Ep_exp, Ep_total, Ep_net | |||
Metering | Energy & Demand | Reactive Energy | Eq_imp, Eq_exp, Eq_total, Eq_net | |||
Metering | Energy & Demand | Apparent Energy | Es | |||
Metering | Energy & Demand | Demand | Dmd_P, Dmd_Q, Dmd_S, Dmd_I1, Dmd_I2, Dmd_I3 | |||
TOU | Time of Use | Energy/max demand | TOU, 4 Tariffs, 12 Seasons, 14 Schedules | |||
TOU | Daylight Savings Time | Two formats adjust | Month/Day/Hour/Minute Month/Week/First few weeks/Hour/Minute |
|||
Monitoring | Waveform Capture | voltage and current Waveform | Trigger, Manual, DI change, Sag/Dips, Swell, Over Current | |||
Monitoring | Power Quality | Voltage Unbalance Factor | U_unbl | |||
Monitoring | Power Quality | Current Unbalance Factor | I_unbl | |||
Monitoring | Power Quality | Voltage THD | THD_V1,THD_V2,THD_V3, THD_Vavg | |||
Monitoring | Power Quality | Current THD | THD_I1, THD_I2, THD_I, THD_Iavg | |||
Monitoring | Power Quality | Individual Harmonics | Harmonics 2nd to 63rd (31st for Acuvim II) | |||
Monitoring | Power Quality | Voltage Crest Factor | Crest Factor | |||
Monitoring | Power Quality | TIF | THFF | |||
Monitoring | Power Quality | Current K factor | K Factor | |||
Monitoring | Statistics | MAX with Time Stamp MIN with Time Stamp |
Each phase of V & l; Total of P, Q, S, PF & F; Demad of P,Q & S; Each phase THD of V & I; Unbalnce factor of V & I |
|||
Others | Alarm | Over/Under Limit Alarm | V, I, P, Q, S, PF, V_THD & I_THD each phase and total or average; Unbalance factor of V & I; load type; Analog Input of each channel | |||
Others | Power Quality Event logging | SAG/DIPS,SWELL | Voltage | |||
Others | Data Logging | Data Logging 1 Data Logging 2 Data Logging 3 |
F, V1/2/3/lnavg, V12/23/13/lavg, I1/2/3/n/avg, P1/2/3/sum,Q1/2/3/sum, S1/2/3/sum, PF1/2/3, PF, U_unbl, I_unbl, LoadType, Ep_imp, Ep_exp, Ep_total, Ep_net, Eq_imp, Eq_exp, Eq_total, Eq_net, Es, THD_V1/2/3/avg, THD_I1/2/3/avg, Harmonics2nd to 63rd, Crest Factor, THFF, K Factor, sequence and phaseangles, DI counter, AI, AO, Dmd P/Q/S, Dmd I1/2/3 | |||
Others | Onboard memory size | Memory | Bytes | - | 4MB | 4MB |
Others | Communication | RS485 Port, Half Duplex,Optical Isolated | Modbus®-RTU Protocol | |||
Others | Time | Real Time Clock | Year, Month, Date, Hour, Minute, Second | |||
Option Module | I/O Option | Switch Status (DI) | Digital Input (Wet) | Option | Option | Option |
Option Module | I/O Option | Power Supply for DI | 24 Vdc | Option | Option | Option |
Option Module | I/O Option | Relay Output (RO) | NO, Form A | Option | Option | Option |
Option Module | I/O Option | Digital Output (DO) | Photo-MOS | Option | Option | Option |
Option Module | I/O Option | Pulse Output (PO) | By using DO | Option | Option | Option |
Option Module | I/O Option | Analog Input (AI) | 0(4)~20mA, 0(1)~5V | Option | Option | Option |
Option Module | I/O Option | Analog Output (AO) | 0(4)~20mA, 0(1)~5V | Option | Option | Option |
Option Module | Communication | Ethernet | 10M/100M, Modbus-TCP, HTTP Webpage, Email | Option | Option | Option |
Option Module | Communication | Profibus-DP | Profibus-DP/V0 | Option | Option | Option |
Option Module | Communication | RS485 Module | Additional Modbus RTU | Option | Option | Option |
As the need to better understand power and energy consumption increases, Accuenergy continues to offer a simple and effective software compliment to our metering products. Combining their meters with the Acuview software suite allows Accuenergy to offer one of the most powerful yet cost effective metering and monitoring solutions in the market.
Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim II-D-5A-P1 Intelligent Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc.